HOT WATER MODELS VHS-30 THROUGH VHS-180
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1-
latest edition. The installation must also conform to the addi-
tional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having jurisdic-
tion, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be installed,
connected, serviced and repaired by a trained, experienced
service technician, familiar with all precautions required for
gas-fired equipment and licensed or otherwise qualified, in
compliance with the authority having jurisdiction.
WARNING
The venting system of this boiler is under positive pressure
when it is connected to the outdoors with 3" diameter pipe.
Leakage from this system can be hazardous and if not avoid-
ed can result in death or serious injury. In addition to the rec-
ommendations within this manual and the User’s Information
Manual, the venting system, from the blower to the outdoor
discharge, must be carefully checked annually by a qualified
service agency.
This manual must be left with owner and
should be hung on or adjacent to the boiler
for reference.
VICTORY II
Models with Intermittent Pilot System – Spark Ignition
INSTALLATION AND OPERATING INSTRUCTIONS
Publication No. VHS-41 Rev.B Part No. 44-0849 Printed 1013
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Dimensions, Rating and Orifice Sizes . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location and Foundation . . . . . . . . . . . . . . . . . . . . .3
Minimum Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Boiler Room Air Supply and Ventilation . . . . . . . . . . . . . . .4
Flue Gas Venting Requirements . . . . . . . . . . . . . . . . . . . . . . .4
Category II and III Venting:
Venting Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Flue Length Restriction . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Category I Venting:
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Vent Connector Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Venting System Regular Inspection . . . . . . . . . . . . . . . . . . . .14
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Boiler Water Temperature Control . . . . . . . . . . . . . . . . . . .19-23
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Piping a Heating-Cooling System . . . . . . . . . . . . . . . . . . . . .26
Operating Instructions:
Filling and Venting Water Systems . . . . . . . . . . . . . . . . . .27
Initial Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Operating Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Burner Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Safety Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Sequence of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
General Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . .32
Appendix A and B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
WARNING
SEE “WARNING” ON PAGE 3 FOR LIQUEFIED
PETROLEUM (L.P.) PROPANE GAS-FIRED BOILERS
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS
AND STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
Vue de la page 0
1 2 3 4 5 6 ... 35 36

Résumé du contenu

Page 1 - VICTORY II

HOT WATER MODELS VHS-30 THROUGH VHS-180GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASESThe installation must conform to the requirements

Page 2

VICTORY II VHS Models10CATEGORY I VENTING (Natural Draft Chimney andType “B” Venting)1. InstallationModel VHS-90, VHS-120, VHS-150 and VHS-180 may bev

Page 3

VICTORY II VHS Models11Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)Chimneys not exposed to the outdoors below the roof line. (5&quo

Page 4

VICTORY II VHS Models12Figure 9.

Page 5

VICTORY II VHS Models13Figure 10.

Page 6 - ProTech FasNSeal System

VICTORY II VHS Models14VENTING SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosionand/or physical damage. A qualifie

Page 7

VICTORY II VHS Models15Figure 11a. Wiring diagram for boilers equipped with Hydrolevel Hydrostat ControlFigure 11b.5. Indirect External Water HeaterIf

Page 8

VICTORY II VHS Models16Figure 12.Figure 13. Multizoning of VHS boilers zone valve system using V8043E/F zone valves

Page 9

VICTORY II VHS Models17Figure 14.Figure 15.

Page 10 - VICTORY II VHS Models

VICTORY II VHS Models18Figure 16.Figure 17. Piping Arrangement

Page 11

VICTORY II VHS Models19NOTE: Settings can be checkedusing the TEST/SETTINGS Button.SETTING THE HIGH LIMITThe high limit is factory set at190°F. To adj

Page 12

VICTORY II VHS Models2NOTE: Height dimensions increase by 13⁄4" and depth increases to 221⁄4" when combustible floor kit is used.Natural #4

Page 13

VICTORY II VHS Models20NOTE: The Program Mode – Pro – is accessed by turning theLO TEMP dial to a position just above OFF.THERMAL PRE-PURGEThermal Pre

Page 14

VICTORY II VHS Models21OPTIONAL FEATURES ContinuedCIRCULATOR ACTIVATION OPTIONSWhen in the default mode, the HydroStat activates the circulator (C1/C2

Page 15

VICTORY II VHS Models22OPTIONAL FEATURES ContinuedRESTORE FACTORY DEFAULT SETTINGSTo restore all features to the factory default settings (see followi

Page 16

VICTORY II VHS Models23u TEMP ACTIVE Indicates that theFuel Smart HydroStat control is pow-ered and that the temperature functionis active.v TEMP HIG

Page 17

VICTORY II VHS Models24WATER PIPINGAlways follow good piping practices. Observe minimum 1" clearance to combustibles around all uninsulated hot w

Page 18

VICTORY II VHS Models25Figure 19. Zoning with zone valves, optional indirect DHW tank

Page 19

VICTORY II VHS Models261. Supply and ReturnFor tapping sizes see dimensions on page 2. Shut-offvalves are recommended.2. Circulating SystemsVictory II

Page 20 - OPTIONAL FEATURES

VICTORY II VHS Models27BEFORE FIRING BOILER, make these checks:1. System is full of water. Air is vented or purged.2. Relief valve is installed in ac

Page 21 - OPTIONAL FEATURES Continued

VICTORY II VHS Models28The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas, is tabu-lated in gas rate

Page 22

VICTORY II VHS Models291. High Limit Control TestSet thermostat high enough for water temperature toreach high limit control setting of water temperat

Page 23

VICTORY II VHS Models3INSTALLATION REQUIREMENTSThe installation must conform to the requirements of theauthority having jurisdiction or, in the absenc

Page 24

VICTORY II VHS Models30C. PipingCheck the following:1. Water piping and accessories for leaks. Slightestleaks should be corrected.2. System to be full

Page 25

VICTORY II VHS Models31THERMOSTAT CALLS FOR HEATCIRCULATOR ONIGNITION SPARK STARTS AND PILOTVALVE OPERATOR OPENSTHERMOSTAT CALLS FORHEAT ENDSCIRCULATO

Page 26

VICTORY II VHS Models32BURNERS FAIL TO OPERATECAUSE REMEDY1. Gas supply valve shut off 1. Open gas valve2. No power, main electric switch open 2. Clos

Page 27 - Instructions

VICTORY II VHS Models33DELAYED IGNITIONCAUSE REMEDY1. Pilot flame too low 1.Adjust pilot flame2. Excessive primary air 2.Adjust primary air shutter3.

Page 28

VICTORY II VHS Models34APPENDIX AVent System Location and CondensationDrain Requirements1. The venting system shall terminate at least 3 feetabove any

Page 29

VICTORY II VHS Models35

Page 30 - WARNING:

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LT EE, Mississauga, Ontariowww.slantf

Page 31

VICTORY II VHS Models4BOILER ROOM AIR SUPPLY AND VENTILATIONAn ample supply of air is required for combustion and venti-lation. When buildings are ins

Page 32

VICTORY II VHS Models5CATEGORY II AND III VENTING1. Vent MaterialA) The vent system for horizontal or vertical venting (Category II and III) must be U

Page 33

VICTORY II VHS Models6Heat-Fab Saf-T Vent SystemBoilerModel No.MinimumLength, Ft.0 to5500 Ft.Altitudes5500 to7000 Ft.Altitudes7000 to10,000 Ft.Altitud

Page 34

VICTORY II VHS Models7Figure 6. * Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeatedsnowfalls accum

Page 35

VICTORY II VHS Models8Figure 7.

Page 36

VICTORY II VHS Models9Figure 8.