HOT WATER MODELS VHS-30 THROUGH VHS-180GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASESThe installation must conform to the requirements
VICTORY II VHS Models10CATEGORY I VENTING (Natural Draft Chimney andType “B” Venting)1. InstallationModel VHS-90, VHS-120, VHS-150 and VHS-180 may bev
VICTORY II VHS Models11Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)Chimneys not exposed to the outdoors below the roof line. (5&quo
VICTORY II VHS Models12Figure 9.
VICTORY II VHS Models13Figure 10.
VICTORY II VHS Models14VENTING SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosionand/or physical damage. A qualifie
VICTORY II VHS Models15Figure 11a. Wiring diagram for boilers equipped with Hydrolevel Hydrostat ControlFigure 11b.5. Indirect External Water HeaterIf
VICTORY II VHS Models16Figure 12.Figure 13. Multizoning of VHS boilers zone valve system using V8043E/F zone valves
VICTORY II VHS Models17Figure 14.Figure 15.
VICTORY II VHS Models18Figure 16.Figure 17. Piping Arrangement
VICTORY II VHS Models19NOTE: Settings can be checkedusing the TEST/SETTINGS Button.SETTING THE HIGH LIMITThe high limit is factory set at190°F. To adj
VICTORY II VHS Models2NOTE: Height dimensions increase by 13⁄4" and depth increases to 221⁄4" when combustible floor kit is used.Natural #4
VICTORY II VHS Models20NOTE: The Program Mode – Pro – is accessed by turning theLO TEMP dial to a position just above OFF.THERMAL PRE-PURGEThermal Pre
VICTORY II VHS Models21OPTIONAL FEATURES ContinuedCIRCULATOR ACTIVATION OPTIONSWhen in the default mode, the HydroStat activates the circulator (C1/C2
VICTORY II VHS Models22OPTIONAL FEATURES ContinuedRESTORE FACTORY DEFAULT SETTINGSTo restore all features to the factory default settings (see followi
VICTORY II VHS Models23u TEMP ACTIVE Indicates that theFuel Smart HydroStat control is pow-ered and that the temperature functionis active.v TEMP HIG
VICTORY II VHS Models24WATER PIPINGAlways follow good piping practices. Observe minimum 1" clearance to combustibles around all uninsulated hot w
VICTORY II VHS Models25Figure 19. Zoning with zone valves, optional indirect DHW tank
VICTORY II VHS Models261. Supply and ReturnFor tapping sizes see dimensions on page 2. Shut-offvalves are recommended.2. Circulating SystemsVictory II
VICTORY II VHS Models27BEFORE FIRING BOILER, make these checks:1. System is full of water. Air is vented or purged.2. Relief valve is installed in ac
VICTORY II VHS Models28The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas, is tabu-lated in gas rate
VICTORY II VHS Models291. High Limit Control TestSet thermostat high enough for water temperature toreach high limit control setting of water temperat
VICTORY II VHS Models3INSTALLATION REQUIREMENTSThe installation must conform to the requirements of theauthority having jurisdiction or, in the absenc
VICTORY II VHS Models30C. PipingCheck the following:1. Water piping and accessories for leaks. Slightestleaks should be corrected.2. System to be full
VICTORY II VHS Models31THERMOSTAT CALLS FOR HEATCIRCULATOR ONIGNITION SPARK STARTS AND PILOTVALVE OPERATOR OPENSTHERMOSTAT CALLS FORHEAT ENDSCIRCULATO
VICTORY II VHS Models32BURNERS FAIL TO OPERATECAUSE REMEDY1. Gas supply valve shut off 1. Open gas valve2. No power, main electric switch open 2. Clos
VICTORY II VHS Models33DELAYED IGNITIONCAUSE REMEDY1. Pilot flame too low 1.Adjust pilot flame2. Excessive primary air 2.Adjust primary air shutter3.
VICTORY II VHS Models34APPENDIX AVent System Location and CondensationDrain Requirements1. The venting system shall terminate at least 3 feetabove any
VICTORY II VHS Models35
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LT EE, Mississauga, Ontariowww.slantf
VICTORY II VHS Models4BOILER ROOM AIR SUPPLY AND VENTILATIONAn ample supply of air is required for combustion and venti-lation. When buildings are ins
VICTORY II VHS Models5CATEGORY II AND III VENTING1. Vent MaterialA) The vent system for horizontal or vertical venting (Category II and III) must be U
VICTORY II VHS Models6Heat-Fab Saf-T Vent SystemBoilerModel No.MinimumLength, Ft.0 to5500 Ft.Altitudes5500 to7000 Ft.Altitudes7000 to10,000 Ft.Altitud
VICTORY II VHS Models7Figure 6. * Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeatedsnowfalls accum
VICTORY II VHS Models8Figure 7.
VICTORY II VHS Models9Figure 8.