IMPORTANT
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph
entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE
GAS-FIRED BOILER LOCATION" on page 4 of this
instruction book.
The above warning does not apply to
NATURAL gas-
fired boilers.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1-latest edition. The installation must also
conform to the additional requirements in this Slant/Fin
Instruction Book.
In addition where required by the authority having juris-
diction, the installation must conform to American
Society of Mechanical Engineers Safety Code for
Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be
installed, connected, serviced and repaired by a
trained, experienced service technician, familiar with all
precautions required for gas-fired equipment and
licensed or otherwise qualified, in compliance with the
authority having jurisdiction.
WARNING
The venting system of this boiler is under positive pres-
sure. Leakage from this system can be hazardous and if
not avoided can result in death or serious injury. In addi-
tion to the recommendations within this manual and the
User’
s Information Manual, the venting system, from the
blower to the outdoor discharge, must be carefully
checked annually by a qualified service agency.
This manual must be left
w
ith owner and should be
h
ung on or adjacent to
t
he boiler for reference.
VICTORY VSPH
INSTALLATION AND OPERATING INSTRUCTIONS
Printed in U.S.A. 207 Part No. 455035 Publication No. VSPH-40 Rev. A
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
DIRECT-VENT SEALED COMBUSTION BOILERS
HOT WATER MODELS VSPH-60 THROUGH VSPH-180
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes ........................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation......................................5
Flue gas Venting Requirements..................................................5
Vent Material ..............................................................................5
Air Intake Material ......................................................................6
Flue and Air Intake Restrictions .................................................6
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance..................................8
Non-Direct Vent Vertical Venting.................................................8
Direct Vent Installation ................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.......................................8
Direct Vent, Venting and Air Intake through a Roof..................13
Venting and Air Intake Regular Inspection ...............................15
Gas Piping ................................................................................15
Electrical Wiring........................................................................15
Multi Zoning ..............................................................................18
Water Piping .............................................................................18
Wiring Diagram.........................................................................16
Operating Instructions...............................................................19
Gas Input Rate Adjustment ......................................................20
Boiler Control............................................................................22
Sequence of Operation.............................................................21
Status of Indicator Lights (LED’s).............................................22
Safety Check ...........................................................................23
Care and Maintenance .............................................................24
General Troubleshooting Guide...........................................25-27
®
Vue de la page 0
1 2 3 4 5 6 ... 27 28

Résumé du contenu

Page 1 - VICTORY VSPH

IMPORTANTREAD ALL OF THE FOLLOWINGWARNINGS AND STATEMENTSBEFORE READING THEINSTALLATION INSTRUCTIONSWARNINGLIQUEFIED PETROLEUM (L.P.)PROPANE GAS-FIRED

Page 2 - RATINGS AND DIMENSIONS

VICTORY VSPH Models10VICTORY VSPH MODELS- NON- DIRECT VENT, VENTING THROUGH A ROOFAll joints must be liquid and pressure tight. Use U/L listed single

Page 3 - Base Assemb

VICTORY VSPH Models11VICTORY VSPH MODELS- NON - DIRECT VENT, UTILIZING AN EXISTING CHIMNEY AS A CHASEAll joints must be liquid and pressure tight. Use

Page 4

VICTORY VSPH Models12VICTORY VSPH MODELS - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&quo

Page 5

VICTORY VSPH Models13Figure 11.Vent/Air Intake Termination10. From inside, install inside termination plate using 4 screws. Make sure the 4" coll

Page 6

VICTORY VSPH Models14Figure 12. Direct vent, venting and air intake through a roof.VICTORY VSPH MODELS DIRECT VENT, VENTING AND AIR INTAKE THROUGH A R

Page 7

VICTORY VSPH Models15VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosionand/or physical damage

Page 8 - (text continued p.13)

VICTORY VSPH Models16PILOTBURNERBURNERMODEL UT-1107MODEL UT-1107P5P5P4P4P1P1P6P6P2P2P3P3INTEGRATED BOILER CONTROLINTEGRATED BOILER CONTR OLP6P6THERMOS

Page 9

VICTORY VSPH Models17MULTIZONING OF VSPH BOILERZONE VALVE SYSTEM USING V8043E/F ZONE VALVESFigure 14.MULTIZONING OF VSPH BOILERPUMP ZONING SYSTEM USIN

Page 10 - CTORY VSPH Models

VICTORY VSPH Models182. Power ConnectionA. Remove electrical junction box cover.B. Hot connection lead is black. Neutral connection lead is white.Prop

Page 11

VICTORY VSPH Models195. Cold Water FillPressure reducing (fill) valve and shut-off valve should beinstalled.6. Relief Valve Discharge PipingUse same s

Page 12

VICTORY VSPH Models2NOTE: Height dimensions increase by11⁄2" and depth increases to 281⁄2" whencombustible floor kit is used.Natural #49 50

Page 13

VICTORY VSPH Models20II. Initial StartSafe lighting and other performance criteria were met whentesting various gas manifold and control assemblies us

Page 14 - VICTORY VSPH MODELS

VICTORY VSPH Models21THERMOSTAT CALLS FOR HEATCIRCULATOR ONINDUCER (BLOWER) ONVSPH BOILER SEQUENCE OF OPERATIONBOILER WATER TEMPERATURE ISBELOW HIGH L

Page 15 - At pressure drop of 0.3 in

VICTORY VSPH Models22a. Input for PROPANE is approximately at rating shown on ating plate when manifold pressure is 9-1⁄2" water columnb. Input f

Page 16 - Figure 13b. Boiler control

VICTORY VSPH Models23To reset the lockout condition: Turn down thermostat or turnpower off at disconnect switch for at least 45 seconds, thenrestore p

Page 17 - MULTIZONING OF VSPH BOILER

VICTORY VSPH Models24CARE AND MAINTENANCEThis section must be brought to the attention of the owner bythe installer so that the owner can make the nec

Page 18 - 2” FPT tapping that the

VICTORY VSPH Models25General Troubleshooting Guide For Service PersonnelTOP JACKETTOP JACKETFLUE COLLECTORFLUE COLLECTORINDUCERINDUCERBRUSHBRUSHWARNIN

Page 19

VICTORY VSPH Models26CAUSE8. Defective pressure switch. POWER and PRES SWITCH LED’s flashing9. Defective high limit control10. Defective inducer motor

Page 20 - VSP40-19VSP40-19

VICTORY VSPH Models27D. BURNER SHORT CYCLESCAUSE1. Thermostat heat anticipator set too low.2. Excessive pressure drop due to excess venting or air int

Page 21

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin

Page 22 - O = LED off = LED steady on

VICTORY VSPH Models3LOCATION AND IDENTIFICATION OF PARTSFigure 2. Location and identification of partsBase Assembly

Page 23 - Power LED (Green)

VICTORY VSPH Models4The installation must conform to the requirements of theauthority having jurisdiction or, in the absence of suchrequirements, to t

Page 24

VENTING APPLICATIONVSPH Series are sealed combustion type boilers, they maybeinstalled and vented either as a direct vent boiler which all airfor comb

Page 25

When joining the various components of the above listedvent systems, the manufacturers’ instructions should beclosely followed to insure proper sealin

Page 26

VICTORY VSPH Models7Maximum allowed flue and air intake equivalent length (Feet)forHeat-Fab Saf-T vent system (Including EZ Seal)Boiler ModelNumberPip

Page 27

VICTORY VSPH Models8VENTING INSTALLATIONFollow the vent material manufacturer’s instructions in con-junction with these instructions for venting syste

Page 28 - ©Slant/Fin Corp. 2007

VICTORY VSPH Models9VICTORY VSPH MODELS NON - DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use U/L listed single wall 3&

Modèles reliés VSPH-60