The installation must conform to the requirements ofthe authority having jurisdiction or, in the absence ofsuch requirements, to the National Fuel Gas
Lynx10VENTING INSTALLATIONOnly the PVC/CPVC, polypropylene and approved stainlesssteel materials listed on page 8 may be used for the ventingsystem in
Lynx11NON-DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylen
Lynx12NON-DIRECT VENT, VENTING THROUGH A ROOFAll joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal polypropy
Lynx13NON - DIRECT VENT, UTILIZING AN EXISTINGCHIMNEY AS A CHASEAll joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3
Lynx14DIRECT VENT, SIDEWALL VENTINGAll joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylene or
Lynx15Figure 13a. Vent/Air intake termination; utilizingPVC/CPVC pipe for venting.Figure 13b. Vent/Air intake termination; utilizing stainlesssteel ve
Lynx16VENT/AIR INTAKE TERMINATION FOR PVC/CPVC, OR POLYPROPYLENE VENTING INSTALLATION (P# 840802000) This termination is designed specifically for 3”
Lynx17B. DIRECT VENT - VENTING AND AIR INTAKE THROUGH A ROOFFigure 14 shows typical vertical venting. The vent pipe must pass through the ceiling, fl
Lynx18VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTIONA. Inspect the system regularly for condensation, corrosion, sagging and/or physical damage. A
Lynx19At 30 ft. length of pipe, match required capacity from table onthis page (choose higher capacity, in this case is 152 cu. ft. perhour). Required
BOILER "A" "B" "C" "D"MODELLX-90 6 3/4 3 3/8 2 3/4 16 1/4
Lynx20Figure 16a. Schematic wiring diagram.
Lynx21ARGUS VISION CONTROL NOT USEDNOT USEDT2J12J13SPARK IGNITORSPARKCABLEGROUNDFUSEJ9J6J2J5BOILER CONTROLFigure 16b. Boiler Control.M120V SECTION OFW
Lynx221ENDSWITCHTH-TRMOTOR2TTT T TT TT TT TT T TTTT3456SPACEHEATINGSYSTEMCIRCULATORENDSWITCHTH-TRMOTORZONE 2THERMOSTATV8043E/FENDSWITCHTH-TRMOTORZONE
Lynx23Figure 17c. Multizoning of Lynx boiler; pump zoning system using R882A/B relays.LIL21DISCONNECTSWITCH120V/24VTRANSFORMERFIELD WIRINGTERMINALSON
Lynx24WATER PIPING A. Connection of system to boiler:Primary/secondary piping should be used to ensure theproper flow through the boiler. (See Figures
Lynx25Figure 18. Relief Valve and Low Water Cutoff Installation
Lynx26Table 2. Recommended pump models for domestic hot water tank piping.Figure 19. Boiler water side pressure drop002468101214246810 Head(feet w.c
Lynx27Figure 20. Zoning with circulators.
Lynx28Figure 21. Zoning with zone valves.
Lynx29Figure 22. Piping a heating-cooling system to the boiler and a chiller.
Lynx3MODEDISPLAYAIRINTAKEBOILERSUPPLYWATERBOILERRETURNWATERGAS SUPPLYVALVEVENTBOILERCONTROLUNDER THE COVER TURNBLACK SCREW1/4 TURNTHEN LIFTCONTROL COV
Lynx30OPERATING INSTRUCTIONSI. FILLING AND VENTING WATER SYSTEMSA. Fill the system with water. Vent or purge of air.B. Fire the boiler as soon as poss
Lynx31*"MODE" DISPLAY"TEMPERATURE" DISPLAY (3 DIGITS)"UP" PUSH BUTTON"DOWN" PUSH BUTTON"ENTER" PUSH
Lynx32MODEDISPLAYDESCRIPTION & TEMPERATURE DISPLAYSpace heating supply water temperature could be changed bypressing “Up/Down” button. Settable fr
Lynx33MODE DISPLAYDESCRIPTIONChanging space heating post pump time. Settable from 10 to 900 seconds.(steps of 10 seconds). The default value is 30 sec
Lynx347070 60 -20-10 -3001020304050Outdoor Temp. (°F)WaterSupplyTarget Temp.(°F)185 °F1401501301901801701601201101008090200Slope = 4.0Slope = 3.0Slope
Lynx35III. INITIAL STARTSafe lighting and other performance criteria were met when testingvarious gas manifold and control assemblies used on the Lynx
Lynx36LYNX BOILER SEQUENCE OF OPERATIONTHERMOSTAT CALLS FOR HEATCIRCULATOR(S) ON5 SECOND PRE-PURGE PERIODGAS VALVE REMAINS OPEN. CONTROLCONTINUOUSLY M
Lynx37IV. Check combustion and fuel input rateA. Remove the boiler jacket front panel by turning the black screws 1/4 turn to the open position. Lift
Lynx38ERROR CODE INDICATION REMEDY01Ignition Failure - 3 unsuccessful ignition attempts in a row.Check for steady sparking at electrodes. If spark not
Lynx39B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the condition returns to normal or is fix
Lynx4The installation must conform to the requirements of theauthority having jurisdiction or, in the absence of suchrequirements, to the National Fue
Lynx40ERROR CODE INDICATION REMEDY30Excess Flue TemperatureCheck flue gas temperature, at the maximum firing rate and high water temperature. If the f
Lynx41CARE AND MAINTENANCEThis section must be brought to the attention of the owner by theinstaller so that the owner can make the necessary arrange-
Lynx42GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNELWARNING: Only a trained, experienced service technician should perform troubleshooting. Turn
Lynx43NOTES:
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/ LTE E, Mississauga, Ontariowww.slantf
CONTAMINATION PREVENTIONThe combustion air supply must not be susceptible to contami-nation sources, whether the combustion air comes from theinterior
Lynx6MOUNTING THE BOILER ON A WALLBe sure that the wall is vertically plumb and capable of carryingthe weight of the boiler and the system piping, whe
A. NON-DIRECT VENT INSTALLATION1. Air drawn horizontally from outdoors DIRECTLY throughan outside wall; one louvered opening near the floor andone lou
Lynx8VENT AND AIR INTAKE MATERIALSThe vent and air intake system for direct or non-direct vent instal-lation must be 3” diameter PVC/CPVC schedule. 40
Lynx93. The vent termination is in addition to the allowed equivalent lengths. 4. Minimum vent length is 2 feet of straight pipe, plus one 90˚ elbow t
Commentaires sur ces manuels