MODEL EM-10
ELECTRIC BOILER CONTROL
Publication No. EM-10-40
Printed in U.S.A. 809
Part No. 792820000
OPERATION AND INSTRUCTION MANUAL
The EM-10 Boiler Temperature Control (BTC) is an efficient
boiler operator with a digital LCD display with backlight, a
boiler pump output, an alert output, and four stage outputs.
The control regulates the boiler based upon setpoint, outdoor
reset, and several options for external boiler control.
Features:
Setpoint Operation
Outdoor Reset with Reset Override
Four Stage Outputs
External Control through BMS Signal
External Control through Tekmar Boiler Controls
Boiler Pump Operation
Parallel Piping
Primary Secondary Piping
Display Backlight
See Service Manual (792840000) for:
Tekmar 275 and other External Direct Drive
Operation
Two Setpoint Operation
Dedicated DHW and Parallel Operation
External Target/ Setpoint Operation
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - MODEL EM-10

MODEL EM-10ELECTRIC BOILER CONTROLPublication No. EM-10-40Printed in U.S.A. 809Part No. 792820000OPERATION AND INSTRUCTION MANUALThe EM-10 Boiler Te

Page 2 - How to Use the Data Brochure

10EM-10-40 Operation and Instruction ManualThe installer should test to confirm that no voltage ispresent at any of the wires during in

Page 3 - Symbol Description

11DIP Switch SettingsControl SettingsOutdoor SensorAn optional Outdoor Sensor may be connected to thecontrol. If the sensor is required, conne

Page 4

12EM-10-40 Operation and Instruction ManualApplicationsMode 4 and 5 – Outdoor Reset and Setpoint OperationMode 4 – Outdoor Reset and Setpoint with Par

Page 5

13EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - View MenusseccAnoitpircseDegnaRdleiF metI-60 to 190°F

Page 6

14EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (1 of 3) Item Field Range Description Acc

Page 7

15EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (2 of 3)Item Field Range Description Acce

Page 8 - Setpoint Operation

16EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (3 of 3)Item Field Range Description Acce

Page 9 - Outdoor Reset Operation

17Error Messages (1 of 2)E01The control was unable to read a piece of information from its EEPROM memory. The control will stop operation until all se

Page 10 - Installation

18EM-10-40 Operation and Instruction ManualError Messages (2 of 2)OUTDOOR SENSOR OPEN CIRCUITThe control is no longer able to read the outdoor sensor

Page 11 - Control Settings

19EM-10-40 Operation and Instruction Manual

Page 12 - Applications

This brochure is organized into three main sections.They are: 1) Sequence of Operation, 2) Installation, and3) Control Settings.The Control Settings s

Page 13 - VIEW MENU

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin

Page 14 - ADJUST MENU

3EM-10-40 Operation and Instruction ManualItemNumber FieldDisplays the current value of the selected itemItem FieldDisplays the current item selected.

Page 15

POWERING UP THE CONTROLWhen the control is powered up, the control turns on allsegments in the display for 2 seconds. Next, the sof

Page 16

5EM-10-40 Operation and Instruction ManualMODE 4(Outdoor Reset and Setpoint with Parallel Piping)Mode 4 is designed for outdoor reset and setpoi

Page 17 - Error Messages (1 of 2)

STAGING MODE (STGMODE)The control can operate up to four stages in order tosupply the required target temperature. The method ofstagi

Page 18 - RELOAD FACTORY DEFAULTS

7EM-10-40 Operation and Instruction ManualMinimum Off Time (MIN OFF)The minimum off time is the minimum amount of time thata stage must be off before

Page 19

BOILER OUTLET MAXIMUMThe BOIL OUT MAX setting determines the highest watertemperature allowed at the boiler outlet sensor. The boilerstages are i

Page 20 - Technical Data

9When either mode 4 or 5 is selected, the control usesoutdoor reset to control the water temperature while a heatdemand is present. Outdo