MODEL EM-10ELECTRIC BOILER CONTROLPublication No. EM-10-40Printed in U.S.A. 809Part No. 792820000OPERATION AND INSTRUCTION MANUALThe EM-10 Boiler Te
10EM-10-40 Operation and Instruction ManualThe installer should test to confirm that no voltage ispresent at any of the wires during in
11DIP Switch SettingsControl SettingsOutdoor SensorAn optional Outdoor Sensor may be connected to thecontrol. If the sensor is required, conne
12EM-10-40 Operation and Instruction ManualApplicationsMode 4 and 5 – Outdoor Reset and Setpoint OperationMode 4 – Outdoor Reset and Setpoint with Par
13EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - View MenusseccAnoitpircseDegnaRdleiF metI-60 to 190°F
14EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (1 of 3) Item Field Range Description Acc
15EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (2 of 3)Item Field Range Description Acce
16EM-10-40 Operation and Instruction ManualMode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (3 of 3)Item Field Range Description Acce
17Error Messages (1 of 2)E01The control was unable to read a piece of information from its EEPROM memory. The control will stop operation until all se
18EM-10-40 Operation and Instruction ManualError Messages (2 of 2)OUTDOOR SENSOR OPEN CIRCUITThe control is no longer able to read the outdoor sensor
19EM-10-40 Operation and Instruction Manual
This brochure is organized into three main sections.They are: 1) Sequence of Operation, 2) Installation, and3) Control Settings.The Control Settings s
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin
3EM-10-40 Operation and Instruction ManualItemNumber FieldDisplays the current value of the selected itemItem FieldDisplays the current item selected.
POWERING UP THE CONTROLWhen the control is powered up, the control turns on allsegments in the display for 2 seconds. Next, the sof
5EM-10-40 Operation and Instruction ManualMODE 4(Outdoor Reset and Setpoint with Parallel Piping)Mode 4 is designed for outdoor reset and setpoi
STAGING MODE (STGMODE)The control can operate up to four stages in order tosupply the required target temperature. The method ofstagi
7EM-10-40 Operation and Instruction ManualMinimum Off Time (MIN OFF)The minimum off time is the minimum amount of time thata stage must be off before
BOILER OUTLET MAXIMUMThe BOIL OUT MAX setting determines the highest watertemperature allowed at the boiler outlet sensor. The boilerstages are i
9When either mode 4 or 5 is selected, the control usesoutdoor reset to control the water temperature while a heatdemand is present. Outdo