EUTECTIC EC-10OIL-FIRED WATER BOILERS/NO. 2 OILINSTALLATION AND OPERATING INSTRUCTIONSSAFETY WARNING:KEEP BOILER AREA CLEAR AND FREE FROM COM-BUSTIBLE
EUTECTIC EC-1010when indirect water heaters are used. When anti-freezemust be used, inhibited propylene glycol is recommended.Useful information on th
Electronic Aquastat Control and Honeywell R7184P Primary Single Zone Wiring for Beckett & Carlin Burners Only.EUTECTIC EC-1011
EUTECTIC EC-1012
EUTECTIC EC-1013
EUTECTIC EC-1014Honeywell L 7248C –1030 Aquastat Control Multiple Zoned (Circulator or Zone Valve)Single Zone, Heat Wise or Riello Burner
EUTECTIC EC-1015Honeywell L7248L,Beckett 7600A andHydroLevel 3250 ControlsSee “Adjusting Settings”& “error Codes” forL7248L on page 16
EUTECTIC EC-1016ADJUSTING SETTINGSTo discourage unauthorized changing of Aquastat settings, a procedureto enter the ADJUSTMENT mode is required. To en
BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY† Head settings shown are approximate ONLY. See “START-UP” on page 8.NOTES:(1) Insertion depth is
EUTECTIC EC-1018BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY† Air shutter and head settings shown are approximate ONLY. See “START-UP” on pag
Head Adjustment L1 & L2 Beckett HeadHead Adjustment V1 Beckett Head1. See figure above. The important “Z” dimension is the distance from the leadi
EUTECTIC EC-102Maximum operating pressure 60 psi.All boilers hydrostatically tested — A.S.M.E.* For forced hot water heating systems where the boiler
EUTECTIC EC-10BURNER DATA - RIELLO BURNERS FOR PACKAGED BOILERS ONLY(RIELLO R-40 SERIES W/SHORT TUBE)† Air shutter and head settings shown are approxi
BURNER DATA - RIELLO (continued)REGULATION OF THE TURBULATOR AND AIR SHUTTER FORPROPER COMBUSTIONTurbulator Setting1. Loosen nut, 1, then turn the scr
Notes:
Notes:
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LT D/LTEE, Mississauga, Ontariowww.slantfi
EUTECTIC EC-103THE INSTALLATION INSTRUCTIONS IN THIS MANUALARE ABBREVIATED. SEE THE FRONT COVER OF THISMANUAL FOR REFERENCES TO CODES AND STAN-DARDS.B
EUTECTIC EC-104Sufficient space shall be left clear around the boiler.the minimum recommended dimensions for providingeasy access around the boiler.85
unreliable, CO2and overfire draft* will change unpredictably.DO NOT vent this boiler to the same chimney flue used by afireplace or coal or wood burni
EUTECTIC EC-1066 IN.MAX.12 IN MAXCHIMNEY6 IN.MAX.12 IN MAXCHIMNEYCHIMNEYCHIMNEYFigure 3a.Appliances located in confined spaces. Air frominside the bui
The opening size recommendation just given is for guidanceonly. It is the installer’s responsibility to provide air for combus-tion and ventilation to
EUTECTIC EC-108OIL SUPPLY PIPINGInstall the oil tank or tanks and piping from tank to burner.Follow local codes and practices, INSTALLATION OF OILBURN
II. Filling and venting the water boiler after cleaningA. Refill the system with fresh water.B. Bring water temperature to at least 180° F promptly.C.